Fume Cupboard Energy Saving Tips
Fume cupboards can waste large amounts of energy, but with a little planning and thought some amazing savings can be made at relatively little cost.
Fume cupboard running costs are a combination of:
-
The energy required to extract air from the fume cupboard, i.e. to operate the extract fan.
-
The energy required to replace and condition (cool/heat/filter) air extracted by the fume cupboard.
-
The energy required to power the fume cupboard sockets, alarm panel and lighting. These costs are usually negligible in comparison to the above and are not discussed on this page.
For example, a 1500mm wide fume cupboard, maintaining an average face velocity of 0.5m/sec across a 500mm high sash opening, operating 24hrs a day, 365 days a year will cost approx. £1,650 per year to run.
There are a number of ways of reducing the energy used to operate a fume cupboard. Below are the most common and effective methods, in order of Cost versus Payback:
Multi-speed fume Cupboard Control Systems
The TEL control system, with inverter drive, reduces the volume extracted from the fume cupboard when the sash is less than half-open. With good user discipline energy savings up to 50% are achievable. Because this control system reduces volume by slowing down the extract fan, the extract system needs to be fitted with a correctly sized taper on the end of the discharge stack to ensure sufficient efflux velocity is achieved at the lower speed setting.
The TEL AFA1000 and AFA4000 control system offers additional safety features such as emergency boost and “idle” night speeds. See the TEL Brochure datasheet for more information. The TEL AFA1000 and AFA400 is ideally suited for use with individual extract systems and variable volume extract systems.
Take an In-depth Look

Reduce Sash Opening
The traditional maximum working height of a fume cupboard sash is 500mm from the work surface. By reducing this maximum opening height to 400mm less volume of air is required to achieve the same average face velocity and an instant 20% energy-saving is made. However, depending on the use of the fume cupboard, the reduced opening may restrict access and/or be uncomfortable for the users.
Reduce Hours of Operation of Fume Cupboard
Simply by switching off your fume cupboard overnight and at weekends the energy cost for the above would drop to approx. £360 per year. BMS systems / time-switches can be used to switch off fume cupboards in the user’s absence, however, where experiments are needed to run overnight there should be some method of locally overriding this. Our airflow monitors have built-in controls for remote switching and local override, for just this purpose.
Fume cupboards are sometimes used to replace or complement the general laboratory extraction system. Under these conditions they may be required to run 24hrs a day. However, they rarely need to operate at their full capacity so we recommend the use of an inverter drive (below) to control the extract volume.
Reduce Fume Cupboard Face Velocity
Traditionally, fume cupboards have been specified and installed to achieve an average face velocity of 0.5m/sec. Reducing the face velocity to 0.4m/sec instantly saves 20% extract volume, or 40% if reduced to 0.3m/sec, and a modern, well-designed, aerodynamic fume cupboard, such as our own, will continue to provide excellent containment of fumes at these reduced face velocities. However, great care should be taken when designing the laboratory and operating the fume cupboard, as the robustness of containment (the ability to contain the fumes when subjected to air disturbance by the user, equipment inside the cupboard, local air conditioning units etc) can be more easily compromised at reduced face velocities. For this reason some clients are reluctant to use low velocity fume cupboards.

Inverter Driven Fume Cupboard Extract
The power absorbed by a fan motor varies as the cube of its speed, e.g. slowing a fan motor by 20% saves almost 50% in energy. Inverters are a very reliable, cost-effective and energy-efficient way of controlling the speed of a fan motor.
Traditional extract systems use a fan motor running at a fixed pole speed and adjust/calibrate the airflow at the fume cupboard via a manual volume control damper in the duct. With an inverter driven fan, the volume control damper is not needed (except where multiple branches exist). At commissioning the inverter is used to fine-tune the speed of the extract fan to achieve exactly the required face velocity.
Inverters offer many additional advantages over traditional control systems, including on-board diagnostics, simplified wiring, improved protection and reliability and easy remote monitoring/control. Used in conjunction with a Fumair control system additional features are exploited to enhance safety and performance, such as “idle” speeds to maintain a permanent low-level of ventilation through the fume cupboards and any attached storage cabinets when they are not in use.
Automatic Sash Closers
Designed for use with VAV or similar systems that monitor sash height, automatic sash closure systems monitor activity in front of the fume cupboard, via a PIR sensor or similar. After a period of no activity a motor will slowly drive the sash to the closed position, allowing the VAV system to reduce the volume of air extracted from the fume cupboard.
Although in principle this would appear to be an excellent idea our experience of such systems is that they are unreliable and unpopular with users , who may, for example, be returning to the cupboard with their hands full of equipment and have to put everything down to open the sash again!


Fume Cupboard VAV System
VAV control systems provide constant face velocity at the fume cupboard, irrespective of sash height. On multiple fume cupboard installations VAVs offer excellent energy savings , but the initial cost of the equipment is high. VAV controls are best installed where multiple fume cupboards are served by one extract system.
Fume Cupboard Extract Systems
The suitability and performance of many of the above energy-saving systems will be determined by the fume extract system they are connected to. For instance, VAV controls are not cost-effective on single fume cupboards served by an individual fume extract fan, whereas the Fumair FlowMaster control system is not suitable for use with a combined fume extract system serving many fume cupboards. Below we list the advantages of individual versus combined fume extract systems.
Individual Extract Systems
Each fume cupboard served by its own extract duct and fan.
-
Optimum energy efficiency is achieved as the extract fan only operates when the attached fume cupboard is in use, unlike VAV systems where the extract fan runs constantly.
-
Should the extract fan fail, or the extract duct become damaged, only the one fume cupboard will be out of service. Unlike a common extract system, all other cupboards will remain operational.
-
No VAV control systems means no moving dampers etc, resulting in better long-term reliability.
-
Although many individual extract systems would suggest a considerably higher installation cost than one large common system, this is not always the case. Smaller ducts cost significantly less than the larger duct used for common extract systems.
-
The most efficient and cost-effective way of controlling fume cupboards on separate extract systems is the Fumair FlowMaster multi-speed extract system. The extract systems will be designed so that at the lowest speed setting, the minimum efflux velocity is still achieved at the point of discharge to atmosphere.
-
No risk of incompatible fumes from different fume cupboards mixing within the duct.

Combined Extract Systems
Many fume cupboards served by one common extract system and fan.
-
Smaller number of discharge stacks means planning approval may be easier to achieve.
-
Best energy efficiency achieved using VAV fume cupboard controllers and bleed dampers.
-
Often easier to route one large duct through the building, rather than multiple smaller ducts.
-
Often cheaper to install than many smaller individual extract systems.
WHAT PEOPLE SAY

Etiologics Ltd, Stoke Poges
I would have no hesitation in recommending Fumair to provide extraction solutions. They are a company that cares, that provide the right product for the task required. 100% service commitment is offered to the customer during the fit and after sales: as standard they go that extra mile

University of Oxford
Fumair have provided Oxford University with an excellent range of fume cupboards for a number of years. Few problems have been experienced and they continue to be one of our preferred suppliers of fume cupboards

Medical Research Council
We have been very happy with Fumair products and services over the years, particularly in regard to specialised extraction systems. We were very impressed with Fumair's technical staff and their knowledge and determination to solve our very specific extraction issues
Some of our Clients